Print Cooling Detail
The section describes what is printed when ☐ Print Cooling Detail is checked in the Print Load Calculations dialog box.
Cooling Load Details - System
The Cooling Loads Details - System table lists each zone in the project and a breakdown of the system cooling loads by type.
The load values are based upon the listed system peak value. The system peak includes the ventilation and plenum loads.
Lighting, equipment, and people loads are not dependent upon the time of day. They are listed in the Cooling Loads Details - Room table to save space.
Each load lists two values. The first is the load in Btu/h, the second is the load as a percentage of the total system cooling load.
-
Location All of the zones in the project. Zones that are part of a zone are indented and listed below the parent zone. If ☐ Print System Loads for Rooms is checked in the Print Load Calculations command, the rooms in the project will also be listed.
-
Peak The month and hour when the peak system cooling load occurs.
-
Plenum The plenum cooling load.
Based upon the following fields in the Query Wall command:
- Wall Type ▾
- Wall Height
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Ceiling Height
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
- ☐ Plenum
- ☐ Plenum Return
- Percentage of Lighting Load to Plenum
Based upon the following fields in the Floor List command:
- Default Ceiling Height
- Floor-to-Floor Height
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Roof The roof cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ Roof
- ☐ Include Roof
- Roof Type ▾
- 🔘 Roof Percent / Area
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
- ☐ Plenum
Based upon the following fields in the Floor List command:
- ☐ Roof
- Roof Type ▾
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Wall The wall cooling load.
Based upon the following fields in the Query Wall command:
- 🔘 Heat Transfer and Solar Gain (Wall)
- Wall Type ▾
- Wall Height
- Lower Wall Type ▾
- Lower Wall Height
- Door Type ▾
- 🔘 Door Percentage / Area / Complex
- Shading Percentage
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Glass The glass cooling load.
Based upon the following fields in the Query Wall command:
- 🔘 Heat Transfer but no Solar Gain (Partition) / 🔘 Heat Transfer and Solar Gain (Wall)
- Glass
- Glass Type ▾
- 🔘 Glass Percentage / Area / Complex
- Shading Percentage
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Glass Zone Type ▾
- Cooling Temperature
- Skylight Type ▾
- Skylight Area
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Vertical Partitions The cooling load from wall partitions.
Based upon the following fields in the Query Wall command:
- 🔘 Heat Transfer but no Solar Gain (Partition)
- Wall Type ▾
- Wall Height
- Partition Temperatures
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Ceiling Height
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Floor List command:
- Default Ceiling Height
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Horizontal Partitions The cooling load from floor and ceiling partitions.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ Floor / Ceiling Partition
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Floor List command:
- ☐ Floor / Ceiling Partition
Based upon the following fields in the Project Info command:
- Latitude
- OSA High Dry
- OSA High Daily Range
-
Ventilation, Sensible The sensible ventilation cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Ventilation Cooling 1
- Ventilation Cooling 2
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
- ☐ OSA is Tempered
- Tempered High Dry Bulb Temperature
Based upon the following fields in the Project Info command:
- Ventilation Calculation Method ▾
- Maximum Room Ventilation Percentage
- OSA High Dry
- OSA High Daily Range
-
Ventilation, Latent The latent ventilation cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Ventilation Cooling 1
- Ventilation Cooling 2
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
- ☐ OSA is Tempered
- Tempered High Dry Bulb Temperature
- Tempered High Wet Bulb Temperature
Based upon the following fields in the Project Info command:
- Ventilation Calculation Method ▾
- Maximum Room Ventilation Percentage
- OSA High Dry
- OSA High Wet
- OSA High Daily Range
-
Infiltration, Sensible The sensible infiltration cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Infiltration Cooling
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Project Info command:
- OSA High Dry
- OSA High Daily Range
-
Infiltration, Latent The latent infiltration cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Infiltration Cooling
- Cooling Temperature
Based upon the following fields in the Zone List command:
- Cooling Temperature
Based upon the following fields in the Project Info command:
- OSA High Dry
- OSA High Wet
- OSA High Daily Range
Cooling Load Details - Room
The Cooling Loads Details - Room table lists each room and zone in the project and a breakdown of the room cooling loads by type.
The load values are based upon the listed room peak value. The room peak does not include the ventilation and plenum loads.
Each load lists two values. The first is the load in Btu/h, the second is the load as a percentage of the total room cooling load.
-
Location All of the zones in the project. Zones that are part of a zone are indented and listed below the parent zone.
-
Peak The month and hour when the peak system cooling load occurs.
If System Type ▾ is set to Constant Volume in the Zone List command, then CV - Sum of Peaks is displayed in the cell. Constant volume zones do not have a peak time.
-
Roof The roof cooling load. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Wall The wall cooling load. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Glass The glass cooling load. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Vertical Partitions The cooling load from wall partitions. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Horizontal Partitions The cooling load from floor and ceiling partitions. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Lighting The lighting cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ Lighting
- Lighting 🔘 Watts / SF / 🔘 Watts
- Percentage to Plenum
Based upon the following fields in the Zone List command:
- ☐ Plenum
- ☐ Plenum Return
- Percentage of Lighting Load to Plenum
Based upon the following fields in the Floor List command:
- Default Ceiling Height
-
Equipment, Sensible The sensible equipment cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ Equipment
- Equipment 🔘 Watts / SF / 🔘 Watts
-
Equipment, Latent The latent equipment cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- Equipment Latent Gain
-
People, Sensible The sensible people cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ People
- People 🔘 SF / Person / 🔘 People
- Activity Level ▾
- Sensible Btu/h / Person
Based upon the following fields in the Zone List command:
- ☐ People Diversity
- People Diversity 🔘 SF / Person / 🔘 People
Based upon the following fields in the Project Info command:
- ☐ Allow Fractional People
-
People, Latent The latent people cooling load.
Based upon the following fields in the Edit Rooms and Room Project Schedule commands:
- ☐ People
- People 🔘 SF / Person / 🔘 People
- Activity Level ▾
- Latent Btu/h / Person
Based upon the following fields in the Zone List command:
- ☐ People Diversity
- People Diversity 🔘 SF / Person / 🔘 People
Based upon the following fields in the Project Info command:
- ☐ Allow Fractional People
-
Infiltration, Sensible The sensible infiltration cooling load. Based upon the same fields as in the Cooling Loads Details - System table described above.
-
Infiltration, Latent The latent infiltration cooling load. Based upon the same fields as in the Cooling Loads Details - System table described above.