Roof, Wall, and Glass Zone Type Tables

The roof, glass, and wall types for the HVAC building load calculations are taken from the 1997 ASHRAE Handbook, Fundamentals. Our calculations use the CLTD method. In the 2001 Fundamentals the load calculation chapter was changed to use the RTS method, but the CLTD method is still considered valid.

The roof types are taken from 1997 ASHRAE Handbook, Fundamentals, Table 31, page 28.42.

The wall types are taken from 1997 ASHRAE Handbook, Fundamentals, Table 33A, pages 28.46-48.

The glass zone types are taken from 1997 ASHRAE Handbook, Fundamentals, Table 35B, page 28.49.

These tables are available below for reference purposes.

The names for the default types are abbreviations. If you have trouble figuring out our system, there is a full description for each type that is displayed when you select it.

Table 31: Roof Types

Use this table to match the properties of your roof to the ASHRAE Roof Type ▾ in the Roof Project Schedule and Roof Master Schedule.

If a parameter combination is not possible, the cell will be blank.

Mass Location**R-Value,
h·ft²·°F/Btu
B7,
1" Wood
C12, 2" HW
Concrete
A3,
Steel Deck
Attic-Ceiling
Combination
Mass inside insulation0 - 52
5 - 102
10 - 154
15 - 204
20 - 255
25 - 30
Mass inside insulation,
suspended ceiling
0 - 55
5 - 108
10 - 1513
15 - 2013
20 - 2514
25 - 30
Mass evenly placed0 - 51211
5 - 10212
10 - 15212
15 - 20422
20 - 25424
25 - 30
Mass evenly placed,
suspended ceiling
0 - 531
5 - 1041
10 - 1552
15 - 2092
20 - 25104
25 - 3010
Mass outside insulation0 - 52
5 - 103
10 - 154
15 - 205
20 - 255
25 - 30
Mass outside insulation,
suspended ceiling
0 - 53
5 - 103
10 - 154
15 - 205
20 - 25
25 - 30

**C12 is considered massive; others are considered nonmassive

Table 33: Wall Types

Use these tables to match the properties of your roof to the ASHRAE Wall Type ▾ in the Wall Project Schedule and Wall Master Schedule. See Table 11 for definitions of the wall material code numbers.

If a parameter combination is not possible, the cell will be blank.

Table 33A: Mass Located Inside Insulation

Stucco and/or
plaster
R-Value,
 h·ft²·°F/Btu 
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.0
2.0 - 2.555
2.5 - 3.0532565
3.0 - 3.55422566
3.5 - 4.054236610465
4.0 - 4.756524661151010
4.75 - 5.56524661151010
5.5 - 6.565251071251110
6.5 - 7.75654511716101111
7.75 - 9.06545117101111
9.0 - 10.7565451171011411
10.75 - 12.75654511111011411
12.75 - 15.010104511111011912
15.0 - 17.5101055111111121016
17.5 - 20.0111059111115161016
20.0 - 23.0111099161115161016
23.0 - 27.01615
Steel or other lightweight sidingR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.0
2.0 - 2.53235
2.5 - 3.0522535
3.0 - 3.55312555
3.5 - 4.05322556355
4.0 - 4.7564225510465
4.75 - 5.565226611566
5.5 - 6.565236611566
6.5 - 7.75652366115610
7.75 - 9.0652366125611
9.0 - 10.756523661256411
10.75 - 12.7565236712611411
12.75 - 15.0652467121011511
15.0 - 17.5106441071011911
17.5 - 20.0101044101110111011
20.0 - 23.0111045111110111016
23.0 - 27.0101116
Face brickR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.0
2.0 - 2.5311
2.5 - 3.051161112
3.0 - 3.551251111121212
3.5 - 4.0512612612121312
4.0 - 4.7561361013101212131116
4.75 - 5.56136111112131316
5.5 - 6.561361111121313
6.5 - 7.75613611111313
7.75 - 9.06131016111313
9.0 - 10.75614101611131416
10.75 - 12.75614101611131416
12.75 - 15.0611161213
15.0 - 17.510111213
17.5 - 20.0101116
20.0 - 23.0111516
23.0 - 27.016

Table 33B: Mass Evenly Placed

Stucco and/or
plaster
R-Value,
 h·ft²·°F/Btu 
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.013133
2.0 - 2.513122445
2.5 - 3.0141222445
3.0 - 3.5112210454
3.5 - 4.011241044
4.0 - 4.751121044
4.75 - 5.5112
5.5 - 6.512410
6.5 - 7.7512411
7.75 - 9.012416
9.0 - 10.75124164
10.75 - 12.751254
12.75 - 15.0225
15.0 - 17.5225
17.5 - 20.0229
20.0 - 23.0249
23.0 - 27.09
Steel or other lightweight sidingR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.013132
2.0 - 2.513121323
2.5 - 3.0141212443
3.0 - 3.511415244
3.5 - 4.01122524
4.0 - 4.751121044
4.75 - 5.5112
5.5 - 6.511210
6.5 - 7.7511411
7.75 - 9.012416
9.0 - 10.7512416
10.75 - 12.75124
12.75 - 15.0125
15.0 - 17.5125
17.5 - 20.0125
20.0 - 23.0249
23.0 - 27.09
Face brickR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.0366
2.0 - 2.531051010
2.5 - 3.0410555101110
3.0 - 3.51151055111115101010
3.5 - 4.0115101055111116101610
4.0 - 4.75111110551611101616
4.75 - 5.51111105101616101616
5.5 - 6.516109101611111616
6.5 - 7.75161191016161616
7.75 - 9.01615910161516
9.0 - 10.7516151010161610
10.75 - 12.75161610101615
12.75 - 15.0161610101615
15.0 - 17.516101516
17.5 - 20.016151516
20.0 - 23.01516
23.0 - 27.015

Table 33C: Mass Located Outside Insulation

Stucco and/or
plaster
R-Value,
 h·ft²·°F/Btu 
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.013132
2.0 - 2.513121323
2.5 - 3.0141212443
3.0 - 3.511415244
3.5 - 4.01122524
4.0 - 4.751121044
4.75 - 5.5112
5.5 - 6.512210
6.5 - 7.7512411
7.75 - 9.012416
9.0 - 10.75124162
10.75 - 12.751244
12.75 - 15.0225
15.0 - 17.5225
17.5 - 20.0225
20.0 - 23.0249
23.0 - 27.09
Steel or other lightweight sidingR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.013132
2.0 - 2.513121323
2.5 - 3.0141212443
3.0 - 3.511415244
3.5 - 4.01122524
4.0 - 4.751121044
4.75 - 5.5112
5.5 - 6.511210
6.5 - 7.7511411
7.75 - 9.012416
9.0 - 10.75124162
10.75 - 12.751244
12.75 - 15.0125
15.0 - 17.5125
17.5 - 20.0125
20.0 - 23.0249
23.0 - 27.09
Face brickR-Value,
h·ft²·°F/Btu
A1A2B7B10B9C1C2C3C4C5C6C7C8C17C18
0.0 - 2.0366
2.0 - 2.531051010
2.5 - 3.0410555101110
3.0 - 3.51151055111115101010
3.5 - 4.0115101055111116101610
4.0 - 4.75111110551611101616
4.75 - 5.51111105101616101616
5.5 - 6.516109101611111616
6.5 - 7.75161191016161616
7.75 - 9.01615910161516
9.0 - 10.7516151010161610
10.75 - 12.75161610101615
12.75 - 15.0161610101615
15.0 - 17.516101516
17.5 - 20.016151516
20.0 - 23.01516
23.0 - 27.015

Table 11 (Partial): Thermal Properties of Wall Materials

Table 33 references wall materials that are defined in this table. The following is a partial transcription of Table 11 that only includes the wall materials referenced.

Code NumberDescriptionLkρcpRMass
A11" Stucco0.08330.40116.00.20.219.7
A24" Face brick0.3330.77125.00.220.4341.7
B71" Wood0.08330.0737.00.61.193.1
B102" Wood0.1670.0737.00.62.396.2
B94" Wood0.3330.0737.00.64.7612.3
C14" Clay tile0.3330.3370.00.21.0123.3
C24" Lightweight concrete block0.3330.2238.00.21.5112.7
C34" Heavyweight concrete block0.3330.4761.00.20.7120.3
C44" Common brick0.3330.42120.00.20.7940.0
C54" Heavyweight concrete0.3331.00140.00.20.3346.7
C68" Clay tile0.6670.3370.00.22.0046.7
C78" Lightweight concrete block0.6670.3338.00.22.0025.3
C88" Heavyweight concrete block0.6670.6061.00.21.1140.7
C178" Lightweight concrete block (filled)0.6670.0818.00.28.3412.0
C188" Heavyweight concrete block (filled)0.6670.3453.00.21.9635.4

L = thickness, ft
k = thermal conductivity, Btu/h·ft·°F
ρ = density, lb/ft³
cp = specific heat, Btu/lb·°F
R = thermal resistance, °F·ft²·h/Btu
Mass = unit mass, lb/ft²

Table 35B: Glass Zone Types

Use this table to match the properties of your room to the Glass Zone Type ▾ in the Room Project Schedule, Room Master Schedule, or the Room List dialog box.

In cases where the effects of the inside shade are negligible, the cell will be blank.

Walls in ZoneFloor CoveringPartition TypeInside ShadeGlass Zone Type
1 - 2CarpetGypsumA
CarpetConcrete blockB
VinylGypsumFullB
VinylGypsumHalf to NoneC
VinylConcrete blockFullC
VinylConcrete blockHalf to NoneD
3CarpetGypsumA
CarpetConcrete blockFullA
CarpetConcrete blockHalf to NoneB
VinylGypsumFullB
VinylGypsumHalf to NoneC
VinylConcrete blockFullB
VinylConcrete blockHalf to NoneC
4CarpetGypsumA
VinylGypsumFullB
VinylGypsumHalf to NoneC