Skip to main content

Neutrals

warning

Neutrals cannot be added to or removed from feeders and branch circuits using ElectroBIM commands. Whether the software includes a neutral is based upon the Revit settings described below.

Distribution Equipment

A neutral is included on the feeder to a piece of distribution equipment based upon the settings of the Distribution System chosen for the equipment.

You can modify the Distribution System settings using the Manage→MEP Settings→Electrical Settings command. From the tree on the left side of the dialog box, select Distribution Systems.

Using the table below as a reference, configure the neutrals for your distribution systems.

Single-Phase
Single Pole
Single-Phase
Two Pole
Three-Phase
NeutralPhase ▾ to Single
Wires ▾ to 2
Phase ▾ to Single
Wires ▾ to 3
L-G Voltage ▾ to not None
Phase ▾ to Three
Wires ▾ to 4
No NeutralN/APhase ▾ to Single
Wires ▾ to 3
L-G Voltage ▾ to None
Phase ▾ to Three
Wires ▾ to 3

Branch Circuits

Revit includes a neutral on branch circuits if the load is unbalanced or if the wiring type requires a neutral.

Edit the family of the device on the circuit, select the connector, and set the System Type to Power - Balanced or Power - Unbalanced as appropriate for the loads on the device. If set to Power - Unbalanced, Revit will include a neutral on the circuit.

To set the neutral requirement, use the Manage→MEP Settings→Electrical Settings command. From the tree on the left side of the dialog box, select Wiring→Wiring Types. For each wire type listed, check or uncheck the ☐ Neutral Required box as appropriate.

To set the Wire Type used to determine whether the branch circuit has a neutral, select a device connected to the circuit. Select the Electrical Circuits tab on the ribbon. In the Properties panel, you can change the Wire Type value.

Video Demonstration