Skip to main content

Fault Calculation Method

The fault calculations are based upon IEEE Std 242-2001: IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems.

The fault calculated is the three-phase line-to-line fault.

Fault=VoltageResistance2+Reactance2Fault = {Voltage \over \sqrt{Resistance^{2} + Reactance^{2}}}

The default feeder and branch circuit ResistanceResistance and ReactanceReactance values are based upon NEC Table 9. These values can be modified in the Wire Sizing command.

The default transformer impedance values are for dry-type indoor transformers. These values can be modified.

The fault calculation includes motor contributions for all devices with a "Motor" load type, such as Single Motor, Multiple Motors, or Heating and Cooling Motor. The motor current is equal to Rated Current×4Rated\>Current \times 4. The X/R ratio of motors is 4. The impedance of the branch circuit wires from the motor to the panel is not included. These values cannot be modified.